LOAD CHART & DG SPECIFICATIONS

KVA Amps Amps KWH KWH Lub oil Acoustic Generator - Specifications
@ 100% @ 80% @ 100% @ 80% after 240 Length Width Height Weight Crane cap  Crane Required  Cable Sq.mm
0.8 PF 0.8 PF 0.8 PF 0.8 PF hours In Feet MT MT Number Armoured       3 1/2 core
60 84 67 48 38 12 12 5 6.5 2.5 8 1 70x1
100 139 111 80 64 20 14 6.5 7.5 3.5 10 1 120x1
125 174 139 100 80 25 14 6.5 7.5 4 12 1 120x1
180 251 200 144 115 35 16 6.5 7.5 4.5 12 1 185x1
250 348 278 200 160 45 16 6.5 8 5 12 1 240x1
250 348 278 200 160 45 19 6.5 8 6 12 1 240x1
250 348 278 200 160 45 16 8.5 8 6.5 12 1 240x1
320 445 356 256 205 50 19 6.5 8 6.5 12 1 300x1
320 445 356 256 205 50 16 8.5 8 6.5 12 1 300x1
380 529 423 304 243 55 19 6.5 8 7 12 1 185x2
400 557 445 320 256 55 19 6.5 8 7 12 1 185x2
500 696 557 400 320 90 19 6.5 8 10 12
14
2
1
185x3
240x2
500 696 557 400 320 90 20 8.5 8 11 12
14
2
1
185x3
240x2
600 835 668 480 384 90 20 8.5 8 11 12
14
2
1
185x3
300x2
750 1044 835 600 480 150 20 8.5 8 12 12 2 185x4
240x3
750 1044 835 600 480 150 24 8.5 9.5 14 12 2 185x4
240x3
1000 1392 1114 800 640 200 24 8.5 9.5 15 12 2 240x4
1000 1392 1114 800 640 200 30 8.5 9.5 16 12 2 240x4
1000 1392 1114 800 640 200 40 8.5 9.5 19 14 2 240x4
1500 2088 1670 1200 960 470 40 8.5 9.5 22 14 2 240x6
  • Our DG sets have electronic power cut-off to control the power drawn by the customers in case set parameter exceeds the limit.
  • We permit a maximum of 80% load at 0.8 PF under normal working conditon.
  • The generator supplied is of 415 volts, 50 hz, 3 phase with 0.8 power factor.
  • In case power factor defers, the load drawn will also be deferred corresponding to power factor.
  • It must always be remembered that overloading & sudden jerk loads are the main cause for the breakdown of any DG Set.
  • The sudden block loading should not cross more than 50% of the DG load capacity.